Electrical Enquiries: 0121 236 5012. Lighting Enquiries: 0121 236 6999
SND Electrical

More Images
Purchase Options
Product Code: Mag816
Product Brand: ESP
RRP : £179.00
Our Price : £159.99
You Save : £19.01
Quantity * :
Click image to enlarge  

Product Details

  • to 16 programmable zones

  • Up to 16 sounder circuits

  • Active end of line monitoring and head removal

  • Up to 32 fire detectors per zone

  • Unlimited number of call points per zone

  • Integral evacuate alarm button

  • Repeater facility

  • ‘Class change’ facility

  • Enable/disable security key

  • One man walk test facility

  • Volt free fire change over relay

  • Individual sounder circuit fault ID

  • Individual zone/sounder isolate

  • Alarm delay options

  • BS5839 and EN54 P2/4 compliant

  • CE certified

  • Requires 1 x 12V batteries

  • ABS casing


NPUTS  Max detectors per zone  32
   Thresholds for zone conditions  0-2 mA (Fault condition)
 2-10 mA (Normal condition)
 10-110 mA (Fire condition)
 110 mA + Short (Fault condition)
 POWER  Mains fail consumption  130mA (1 zone expander)
 260mA (4 zone expander)
   Mains supply  230 VAC ± 10%
   Standby supply  1 x 18ah 12V S.L.A. Batteries
   Power availability  0.7 amps
 OUTPUTS  On board sounder circuits (4)  300mA @ 24V fuse resettable (PTC)
   Sounder expander cards (4)  150mA @ 24V fuse resettable (PTC)
   Fault/fire Relay  Volt free 500mA @ 24V (max load)
   Auxiliary output  24VDC (300mA fused)
 ENVIRONMENT  Working Temperature  0 to 40°C
   Storage Temperature  -20 to 60°C
   Humidity  0-93%
   Dimensions (mm)  456W 350H 125D
   Weight  4.2 KG


                   Fire Zone / Sounder Output Matrix
 Number of
 zone cards fitted
 Number of
 sounder cards fitted
 Number of zone  Number of
 sounder outputs
2 0 8 4
3 0 12 4
4 0 16 4
2 1 8 8
3 1 12 8
1 2 4 12
2 2 8 12
1 3 4 16

NB. The MAG816 features 4 sounder circuits. Space is provided for up to 4 extra expansion cards of any combination. Sounder cards carry 4 sounder circuits, Zone cards carry 4 fire zones. The MAG816 is supplied as standard with 8 fire zones and 4 sounder circuits.